Frage 1
Frage
What type of system consists of cables that were installed in an air-handling space prior to mandated use of cables that meet the flame-spread and smoke-index requirements of codes, standards & regulations?
Antworten
-
Grandfathered System
-
Abandoned cable System
-
Riser Cable System
-
Non-Plenum Cable System
Frage 2
Frage
What are the 2 key components of an optical fiber?
Antworten
-
Core & Cladding
-
Core & Acrylate
-
Cladding & Acrylate
-
Core & Buffer
Frage 3
Frage
The [blank_start]F Rating[blank_end] is the amount of time in hours the firestopping system can prevent flames from passing through the system.
Antworten
-
F Rating
-
T Rating
-
L Rating
Frage 4
Frage
This is the establishment of a reference for the electrical power source (AC or DC), electrical equipment or both
Antworten
-
Grounding
-
Bonding
-
Electrode System
-
TMGB
Frage 5
Frage
The [blank_start]L Rating[blank_end] indicates a firestops ability to provide an effective smoke seal.
Antworten
-
L Rating
-
F Rating
-
T Rating
Frage 6
Frage
This provides a quick graphical representation of how a circuit is laid out
Antworten
-
Circuit Layout Record
-
Cutover Plan
-
As-built
Frage 7
Frage
A Consolidation Point (CP) should serve up to 24 work areas?
Frage 8
Frage
How many walls of a TR should have fire-retardant plywood?
Frage 9
Frage
Cross-Connect Field Colors: Second-Level Backbone
Frage 10
Frage
All ferrous metal pathways must be bonded at both ends regardless of length when containing a bonding conductor?
Frage 11
Frage
This amount of current will cause breathing to become difficult
Antworten
-
2-3mA
-
10mA
-
50-100mA
-
100mA
Frage 12
Frage
Who's responsibility is it to provide safety training for its employees?
Antworten
-
Employee's Organization
-
Employee
-
OHSA
-
Customer
Frage 13
Frage
Widening or spreading out of modes in a light pulse as it progresses along the optical fiber
Antworten
-
Dispersion
-
Core
-
Photons
-
Modal Bandwidth
Frage 14
Frage
This type of cutover is one continuous process until competed
Antworten
-
Flash Cutover
-
Phased Cutover
-
Complete Shutdown
-
Continuous Cutover
Frage 15
Frage
This type of backbone cabling distributes telecommunications services between telecommunications spaces within a single building
Antworten
-
Intrabuilding
-
Interbuilding
-
Fiber Optic
Frage 16
Frage
What is the width of the TMGB
Antworten
-
3.94 inches
-
3.95 inches
-
3.93 inches
-
4 inches
Frage 17
Frage
The ITS installer can substitute products that are not part of the qualified firestop assembly
Frage 18
Frage
This firestop is used primarily for large air handling & exhaust vents
Antworten
-
Blankets
-
Spray
-
Pillows
-
Foam
Frage 19
Frage
This type of cutover procedure has portions of the old system transferred to the new system in groups
Antworten
-
Flash Cutover
-
Phased Cutover
-
Staged Cutover
-
Continuous Cutover
Frage 20
Frage
What is the information carrying capacity of a system
Antworten
-
Bandwidth
-
Megabit
-
Megahertz
-
Decibel
Frage 21
Frage
What is the maximum length of FMT
Antworten
-
20 feet
-
10 feet
-
15 feet
-
25 feet
Frage 22
Frage
26 AWG has ______ more attenuation
Frage 23
Frage
This is the copper conductor that interconnects the TMGB to TGB
Frage 24
Frage
Cross-Connect Field Colors: Network Connections
Frage 25
Frage
Who should the ITS installer seek guidance from for minimum safety requirements for safe work & employee health
Antworten
-
AHJ
-
Employer
-
OHSA
-
Safety Director
Frage 26
Frage
What is the recommended maximum value for the bonding resistance between any 2 points where bonding exists
Antworten
-
0.1 Ohms
-
1 Ohm
-
10 Ohms
-
0.01 Ohms
Frage 27
Frage
The refractive index of the fiber core is higher than that of the cladding
Frage 28
Frage
This type of backbone consists of cabling that is installed between a MC and IC/HC
Antworten
-
First Level
-
Second Level
-
Interbuilding
-
Fiber Optic
Frage 29
Frage
This is a result from different optical fiber lengths in multimode fiber
Antworten
-
Overfill Launch
-
Modal Dispersion
-
Modal Bandwidth
Frage 30
Frage
This type of protector is used to protect against sneak current
Antworten
-
Primary
-
Secondary
-
Data & Fire Alarm
-
Carbon
Frage 31
Frage
Abandoned cable can become fuel and is a fire hazard
Frage 32
Frage
Cross-Connect Field Colors: First Level Backbone
Frage 33
Frage
Why is copper a preferred conductor (select all correct)
Antworten
-
Economical
-
Offers less resitance
-
Readily available
-
Easy to produce
Frage 34
Frage
This type of protector has a reaction time of 3-5ns
Antworten
-
Gas
-
Carbon
-
Solid State
-
Primary
Frage 35
Frage
The results of a __________ will be used to develop the project schedule and the installation job plan
Antworten
-
Site survey
-
Scope of work
-
Specification
Frage 36
Frage
Humans can hear in what frequency range
Antworten
-
20-20,000Hz
-
20-20,000MHz
-
20-2,000Hz
-
20-2,000MHz
Frage 37
Antworten
-
1 billionth of a meter
-
1 thousandth of a meter
-
1 millionth of a meter
Frage 38
Frage
The primary responsibility of the ___________ is safeguarding personnel, property and equipment from foreign electrical voltages and current
Antworten
-
ITS Installer
-
Qualified Electrican
Frage 39
Frage
When personnel are relocated into temporary office space during retrofits
Antworten
-
Temporary Space
-
Swing-space Phasing
-
Project Relocation
Frage 40
Frage
When are GFCIs required (select all correct)
Frage 41
Frage
What is the movement of information in the form of electrical or optical signals from one point to another through a transport medium
Antworten
-
Transmission
-
Signal Transfer
-
Attenuation
-
Propagation Delay
Frage 42
Frage
More deaths result from flames rather than smoke and toxic gases
Frage 43
Frage
What does OSHA have the authority to do (select all correct)
Antworten
-
Develop, publish & enforce safety regulations
-
Shut down unsafe job site
-
Levy fines against individuals and companies
-
confiscate tools and equipment
Frage 44
Frage
The [blank_start]T Rating[blank_end] is the amount of time in hours the firestopping system can keep the temperature from rising above a specified point
Antworten
-
T Rating
-
F Rating
-
L Rating
Frage 45
Frage
List 3 distinct, yet interconnected grounding systems (Select all correct)
Antworten
-
AC Grounding Electrode System
-
Equipment Grounding System
-
Telecommunications Bonding Infrastructure
-
Supplemental Ground System
Frage 46
Frage
1 cycle in 1 second = ?
Frage 47
Frage
Which fiber is most common for backbone & horizontal runs within buildings and campus environments
Antworten
-
Multimode
-
Singlemode
-
OM2
-
OM1
Frage 48
Frage
If expanding a TR, what must be done prior to removing the wall with equipment/hardware
Frage 49
Frage
What type of ladder is not allowed to be used by an ITS installer
Antworten
-
Aluminum
-
Wood
-
Extension
-
Fiberglass
Frage 50
Frage
What is the diameter of the cladding in multimode fiber cable
Frage 51
Frage
What is the distance limitation of multimode fiber
Antworten
-
2,000 meters
-
3,000 meters
-
1,000 meters
-
10,000 meters
Frage 52
Frage
If an extension ladder is extended 24ft up, then how far should the base be out
Frage 53
Frage
Which transmission method transmits a signal in one direction only
Antworten
-
Simplex
-
Full Duplex
-
Half Duplex
Frage 54
Frage
It is acceptable to use a TE in place of a TR
Frage 55
Frage
Which fiber supports wavelengths of 1310nm, 1490nm, 1550nm & 1625nm
Frage 56
Frage
What is the minimum size of stub up conduits
Frage 57
Frage
How many rungs need to overlap when extending an extension ladder
Frage 58
Frage
What is the measure of analog signal strength
Frage 59
Frage
How far should an extension ladder extend above a work area
Frage 60
Frage
This current will trigger ventricular fibrillation, which causes the heart to repeatedly relax and violently clamp shut (usually results in death)
Antworten
-
100mA
-
200mA
-
50mA
-
50-100mA
Frage 61
Frage
One of the primary functions of the ____________ is to house the floor-serving cross-connections and interconnection
Frage 62
Frage
What is the distance limitation of singlemode fiber
Antworten
-
2,000 meters
-
3,000 meters
-
5,000 meters
-
10,000 meters
Frage 63
Frage
___________ are not dependent on ITS installers
Antworten
-
Customers
-
Employees
-
IT Professionals
Frage 64
Frage
How far must an ITS installer stay away from exposed energized circuits operating at 300-50,000 volts
Frage 65
Frage
Which fiber supports wavelengths of 850nm and 1300nm
Frage 66
Frage
What the 3 distinct ways in which others perceive and employee (select all correct)
Antworten
-
Body language
-
Tone of voice
-
Choice of words
-
Facial expressions
Frage 67
Frage
Chin straps are not allowed to be used with hardhats
Frage 68
Frage
What is the most common fire protection principle
Antworten
-
Compartmentation
-
Suppression
-
Detection
Frage 69
Frage
Which fiber generally uses LED and VCSEL light sources
Frage 70
Frage
What is the diameter of the acrylate coating in fiber cable
Frage 71
Frage
What is the typical lifespan of a hard hat
Antworten
-
5 years
-
1 year
-
3 years
-
2 years
Frage 72
Frage
What is the most common tight buffer diameter
Frage 73
Frage
Tone of voice is ____% of communication perceptions
Frage 74
Frage
If using a MUTOA, what is the maximum length of a 24AWG, stranded work area cable if the horizontal cable is 70 meters
Antworten
-
22 meters
-
25 meters
-
5 meters
-
27 meters
Frage 75
Frage
Which method transmits in either direction but in only 1 direction at a time
Antworten
-
Simplex
-
Half duplex
-
Full duplex
Frage 76
Frage
Stickers are allowed to be placed on hard hats
Frage 77
Frage
Tight buffer fiber is only installed in multimode fiber
Frage 78
Frage
What is the maximum amount of moisture allowed in plywood backboards
Frage 79
Frage
Which type of fiber requires a furcation kit
Antworten
-
Tight Buffer
-
Multimode
-
Loose Tube
-
Singlemode
Frage 80
Frage
Select all approved eye protection
Antworten
-
Glasses
-
Goggles
-
Full Face Shield
Frage 81
Frage
This type of fiber consists of up to 24 strands bundled together in a single line that is color coded
Antworten
-
Ribbon
-
Air blown
-
Tight buffer
-
Loose tube
Frage 82
Frage
These are to be installed on exposed circuits as near as possible to the point at which the exposed cables enter the bulding
Frage 83
Frage
This firestop product is intumescent, metal back and used to seal large openings
Antworten
-
sheets
-
putty
-
blankets
-
pads
Frage 84
Frage
This firestop material is a putty that is used to seal the back of outlet boxes
Frage 85
Frage
This firestop material is intumescent used for plastic piping, insulated metal piping or cable bundles
Frage 86
Frage
This firestop material is intumescent but mostly endothermic, soft and pliable. It comes in bars and sticks
Frage 87
Frage
This firestop material can be intumescent, endothermic or ablative. It comes in tubes and can up to 2 weeks to to cure. It is used for permanent installations
Frage 88
Frage
This firestop material is regarded as temporary and requires wire restraints to pass the hose test
Frage 89
Frage
This firestop material incorporates putty and is referred to as a pipe choke system
Frage 90
Frage
This firestop material may be intumescent, endothermic or ablative. It is a 2 part mixing with fast curing time
Frage 91
Frage
Select the 3 types of centralized fiber cabling implementations
Antworten
-
Pull-through
-
Interconnection
-
Splice in the TR
-
Home Run
Frage 92
Frage
This is a property of an electrical force field built around a conductor that opposes and changes in current flow in a circuit
Antworten
-
Inductance
-
Capacitance
-
Resistance
-
Impedance
Frage 93
Frage
Words are _____% of communication perceptions
Frage 94
Frage
Air-blown systems are designed & manufactured for an expected operating lifetime of how many years
Frage 95
Frage
What refers to the amount of information that can be transported over the media
Antworten
-
Megahertz
-
Megabit
-
Decibel
Frage 96
Frage
This current causes the heart the clamp shut and severe burns occur on the skin and hair
Antworten
-
100mA
-
200mA
-
50-100mA
-
50mA
Frage 97
Frage
An ITS installer is allowed to leave a personnel lift with a safety belt with a non-locking keeper
Frage 98
Frage
Increasing the length of fiber or wavelength of the light source will decrease bandwidth
Frage 99
Frage
Open top cable supports are typically intended to support how many cables
Frage 100
Frage
Cross-Connect Field Colors: Miscellaneous
Frage 101
Frage
What is the basic unit of inductance
Frage 102
Frage
There is no mandatory standard to identify the color coding for fiber
Frage 103
Frage
This firestop material is used in situations where a cable tray containing critical power or data cables must remain in operation during a fire
Antworten
-
Blankets
-
Sprays
-
Pillows
-
Putties
Frage 104
Frage
According to standards, horizontal fiber cable is normally ____________
Antworten
-
Multimode
-
Singlemode
-
Tight buffer
-
Loose tube
Frage 105
Frage
What is the minimum bend radius of a fiber cable, with up to 4 strands, during installation
Antworten
-
1 inch
-
2 inch
-
4 x diameter of cable
-
10 x diameter of cable
Frage 106
Frage
What is the minimum bend radius of a fiber cable, with up to 4 strands, at rest
Antworten
-
1 inch
-
2 inch
-
4 x diameter of cable
-
10 x diameter of cable
Frage 107
Frage
What is the minimum bend radius of interbuilding fiber during installation
Antworten
-
10 x diameter of cable
-
15 x diameter of cable
-
20 x diameter of cable
Frage 108
Frage
What is the minimum bend radius of a fiber backbone cable at rest
Antworten
-
15 x diameter
-
10 x diameter
-
20 x diameter
Frage 109
Frage
What is the minimum bend radius of an intrabuilding fiber during installation
Antworten
-
10 x diameter
-
15 x diameter
-
20 x diameter
Frage 110
Frage
Which test instruments can be used to test fiber while it is still on the reel (select all correct)
Frage 111
Frage
Which fiber test instrument does not require access to both ends of the fiber while testing on the reel
Frage 112
Frage
Bonding conductors are designed to intentionally carry AC ground fault current or lightning strike current
Frage 113
Frage
What is the maximum length for horizontal fiber runs
Antworten
-
90 meters
-
100 meters
-
2,000 meters
-
3,000 meters
Frage 114
Frage
Lift belts give the user added strength
Frage 115
Frage
This administration addresses infrastructure with multiple buildings at a single site
Antworten
-
Class 1
-
Class 2
-
Class 3
-
Class 4
Frage 116
Frage
It is recommended to order innerduct without a pull sting preisntalled
Frage 117
Frage
Select all approved types of hearing protection
Frage 118
Frage
This type of protector has a reaction time of 15ns or more
Antworten
-
Gas tubes
-
Solid state
-
Carbon blocks
Frage 119
Frage
This is the property of conductors that allows storage of electric charges when potential differences exist between conductors
Antworten
-
Capacitance
-
Inductance
-
Resistance
-
Impedance
Frage 120
Frage
Body language is ______% of communication perceptions
Frage 121
Frage
This firestop material will develop a hard char that resists erosion from fire and flames
Antworten
-
Ablative
-
Intumescent
-
Endothermic
Frage 122
Frage
This administration addresses infrastructure with one or more telecommunication spaces in a single building
Antworten
-
Class 1
-
Class 2
-
Class 3
-
Class 4
Frage 123
Frage
Fall protection is required at which height
Frage 124
Frage
Which is the required physical topology for SCS
Frage 125
Frage
(2) 1.5 inch and (1) 1 inch innerducts are recommended to be placed inside what size conduit
Antworten
-
3 inch
-
2 inch
-
4 inch
-
6 inch
Frage 126
Frage
Cross-Connect Field Colors: Horizontal Cable
Frage 127
Frage
A PFAS (personal fall arrest system) includes a full body harness, a shock absorbing lanyard & secure anchorage point capable of supporting ______ pounds
Antworten
-
2,500lbs
-
5,000lbs
-
3,000lbs
-
1,000lbs
Frage 128
Frage
The service loop is used to relieve all tension of the fiber cable
Frage 129
Frage
What is allowed to be used to mend torn clothing
Antworten
-
duct tape
-
electrical tape
-
tie wraps
Frage 130
Frage
How much horizontal fiber should be left at the work area
Antworten
-
1 meter
-
2 feet
-
18 inches
-
12 inches
Frage 131
Frage
How much fiber slack should be left in a cabinet within a TR
Antworten
-
10 meters
-
3 feet
-
1 meter
-
3 meters
Frage 132
Frage
Capacitance is measured in ________
Frage 133
Frage
Plywood backboards should be mounted at _____ AFF
Antworten
-
8 inches
-
12 inches
-
6 inches
-
18 inches
Frage 134
Frage
This current will produce a tingling of the skin
Frage 135
Frage
When blowing fiber, what carries the cable down the tube
Antworten
-
fluid drag
-
air pressure
-
vacuum
Frage 136
Frage
What describes the amount of information a fiber is capable of transporting
Antworten
-
Modal Bandwidth
-
Dispersion
-
Megahertz
Frage 137
Frage
Which method transmits a signal in both directions at the same time
Antworten
-
Full duplex
-
Half duplex
-
Simplex
Frage 138
Frage
What type of entrance pathway preserves the aesthetic appearance of the building and is economical over the life cycle
Antworten
-
Underground
-
Buried
-
Aerial
-
Wireless
Frage 139
Frage
Air blown fiber shall not be used for outside plant
Frage 140
Frage
This administration addresses infrastructure with multiple sites or campuses
Antworten
-
Class 1
-
Class 2
-
Class 3
-
Class 4
Frage 141
Frage
This current will produce a painful shock and muscles can't release the contact
Frage 142
Frage
Which of the following are basic tests to verify each tube prior to blowing fiber (select all correct)
Antworten
-
airflow testing
-
pressure testing
-
continuity testing
Frage 143
Frage
This is required on every 3rd floor and top floor of a multi-story building that has multiple ER/TRs on the same floor
Frage 144
Frage
This serves as the dedicated extension of the building AC grounding electrode system of the telecommunications infrastructure
Frage 145
Frage
What is the typical air pressure when blowing fiber
Antworten
-
150-220psi
-
150-200psi
-
100-150psi
-
200-225psi
Frage 146
Frage
Which splicing method has a low consumable cost
Frage 147
Frage
What is the total opposition to current flow
Antworten
-
Impedance
-
Capacitance
-
Resistance
-
Inductance
Frage 148
Frage
What is the basic unit of digital information
Frage 149
Frage
What type of entrance pathway preserves the aesthetic appearance of the building but is inflexible for future service changes
Antworten
-
tunnel
-
underground
-
buried
-
aerial
Frage 150
Frage
What diameter of toggle bolts should be used when mounting a backboard
Frage 151
Frage
Open top cable supports should be installed to maintain a minimum of _____ inches above ceilings
Frage 152
Frage
Reflectance may be a concern with which type of splicing method
Frage 153
Frage
This administration addresses the needs of premises served by a single ER (the only telecommunication space)
Antworten
-
Class 1
-
Class 2
-
Class 3
-
Class 4
Frage 154
Frage
How much fiber typically should be in a splice tray
Antworten
-
3 feet
-
1-2 meters
-
1-3 meters
-
1 meter
Frage 155
Frage
Identify this fusion
Antworten
-
fuse time too long
-
autofeed too low
-
autofeed too high
-
fuse current too hot
Frage 156
Frage
Identify this fusion
Antworten
-
fuse current too hot
-
autofeed too high
-
good splice
-
autofeed too low
Frage 157
Frage
Identify this fusion
Antworten
-
autofeed too high
-
good splice
-
fuse time too long
-
fuse current too hot
Frage 158
Frage
Identify this fusion
Antworten
-
autofeed too low
-
fuse time too long
-
autofeed too high
-
good splice
Frage 159
Frage
Identify this fusion
Antworten
-
good splice
-
autofeed too high
-
autofeed too low
-
fuse time too long
Frage 160
Frage
What is the maximum splice loss regardless of the methodology
Frage 161
Frage
What is the curing cycle for heat cured connectors
Antworten
-
20 minutes
-
10 minutes
-
5 minutes
-
15 minutes
Frage 162
Frage
24AWG stranded cable ha _______ more attenuation
Frage 163
Frage
Adhesive hardening when terminating anaerobic connectors takes how long
Antworten
-
10-20 seconds
-
15 seconds
-
1 minute
-
5-10 seconds
Frage 164
Frage
True power is measured in ______
Antworten
-
Watts
-
Volts
-
Amps
-
Decibels
Frage 165
Frage
What is the size of the primary acrylate
Frage 166
Frage
Measure of signal loss resulting from the insertion of component, link or channel between transmitter and receiver (often referred to as attenuation)
Antworten
-
Crosstalk
-
Return loss
-
Delay skew
-
Insertion loss
Frage 167
Frage
How far should the toggle bolts be spaced when mounting a backboard
Frage 168
Frage
All electrical activity produces electric & magnetic fields
Frage 169
Frage
What quantifies the bandwidth of a cabling system in a frequency range
Antworten
-
megahertz
-
megabit
-
decibel
Frage 170
Frage
What is the #1 reason for troubleshooting in optical networks
Antworten
-
contamination
-
core alignment
-
poor terminations
Frage 171
Frage
What device converts a digital signal into 2 distinctive analog frequencies
Frage 172
Frage
What is the power range for microscopes to view the end face of an optical fiber connector
Antworten
-
100x-800x
-
100x-200x
-
200x-400x
Frage 173
Frage
What is the ratio expressed in decibels of the power of the outgoing signal to the power of the reflected signal
Antworten
-
Return loss
-
Insertion loss
-
Crosstalk
-
Delay skew
Frage 174
Frage
This is the grounding connection point for telecommunications systems and equipment in the area served by an ER or TR
Frage 175
Frage
The inside bend radius shall be _______ times the ID for conduits 2 inches or less
Frage 176
Frage
This tool is used to inspect the radius of curvature, offset of polish & optical fiber height
Antworten
-
VFL
-
Interferometer
-
OLTS
-
OTDR
Frage 177
Frage
This is the copper conductor that interconnects the TMGB to TGB
Frage 178
Frage
This is the unwanted transfer of a signal's EM energy from one or more circuits to other circuits
Antworten
-
Crosstalk
-
Delay Skew
-
Return Loss
-
Insertion Loss
Frage 179
Frage
This tool can determine end-to-end attenuation & distance to a point of high attenuation during pre-installation testing
Antworten
-
OTDR
-
OLTS
-
VFL
-
Interferometer
Frage 180
Frage
Test equipment uses what to determine the length of a cable
Frage 181
Frage
How far does the conductor need to extend beyond the connector if using a set-screw, pass-through style lug
Frage 182
Frage
Cross-Connect Field Colors: Common Equipment
Frage 183
Frage
What device converts analog data, from a video device, to a digital signal
Frage 184
Frage
The inside bend radius shall be ___ times the ID for conduits greater than 2 inches
Frage 185
Frage
Acceptance testing of optical fiber is most often performed with which tester
Antworten
-
VFL
-
OLTS
-
OTDR
-
Interferometer
Frage 186
Frage
What are unsafe oxygen levels
Antworten
-
below 19.5% and above 23.5%
-
below 20.5% and above 25.5%
-
below 15.5% and above 20.5%
Frage 187
Frage
Time for a signal to be transmitted from one end to the other
Antworten
-
Crosstalk
-
Delay Skew
-
Propagation Delay
-
Insertion Loss
Frage 188
Frage
Which entrance pathway has the lowest cabling installation cost
Antworten
-
Aerial
-
Underground
-
Buried
-
Wireless
Frage 189
Frage
For singlemode fiber, out-of-band testing may be accomplished at the _____ nm window
Frage 190
Frage
Difference in propagation delay between slowest & fastest pairs within same cable sheath
Antworten
-
delay skew
-
crosstalk
-
insertion loss
-
return loss
Frage 191
Frage
What is the worst acceptable loss for a mated pair
Frage 192
Frage
95% of mated pairs shall be better than ____dB loss
Frage 193
Frage
This type of protector has a reaction time of 10-15 ns
Antworten
-
Gas
-
Carbon
-
Solid state
-
Fire & data
Frage 194
Frage
There is currently no maximum bandwidth for singlemode optical fiber
Frage 195
Frage
This firestop material expands when exposed to fire or heat
Antworten
-
intumescent
-
ablative
-
endothermic
Frage 196
Frage
This backbone cable distributes telecommunications services between buildings
Antworten
-
interbuilding
-
intrabuilding
Frage 197
Frage
Cross-Connect Field Colors: Demarcation Point
Frage 198
Frage
What is the maximum amount of exposure between the insulation and the bonding connector
Frage 199
Frage
What can be used to neutralize small acid spills
Antworten
-
sodium bicarbonate
-
water
-
milk