Frage 1
Frage
What is the recommended power range for microscopes to view the end face of an optical fiber connector
Antworten
-
100x-200x
-
100x-800x
-
200x-400x
Frage 2
Frage
_____ cabling provides interconnection between TRs, ERs, main terminal space & EF (entrance facilities)
Antworten
-
backbone
-
horizontal
-
riser
Frage 3
Frage
To confine the light within the core by creating a reflective boundary is the purpose of the _______
Frage 4
Frage
This space is a special purpose room that provides and maintains a suitable operating environment for large telecommunications equipment
Frage 5
Frage
During a retrofit, it is not required to remove all abandoned cable
Frage 6
Frage
This space should not serve more than 3,600 sq/ft
Frage 7
Frage
What is the most common specialty fastener used in ITS cabling
Antworten
-
j-hook
-
toggle bolt
-
drive ring
-
bridal ring
Frage 8
Frage
Interbuilding circuits are considered to have lightning exposure unless 1 or more conditions exist (select all correct)
Antworten
-
Buildings close together and sufficiently high
-
Cable run is 140ft or less (underground or in conduit)
-
Area having an avg. of 5 or fewer t-storms per year and earth resistivity less than 100 ohms
Frage 9
Frage
This tester uses Rayleigh scattering & Fresnal reflection to measure the characteristics of an optical fiber
Frage 10
Frage
The ITS installer is allowed to add more firestopping product to get a higher rating
Frage 11
Frage
Cross-Connect Field Colors: Future (Key Telephone Systems)
Frage 12
Frage
What is used to flush electrolyte burns to the skin
Antworten
-
water
-
milk
-
sodium bicarbonate
Frage 13
Frage
Shorter wavelengths of light exhibit greater amounts of attenuation because of Rayleigh scattering
Frage 14
Frage
Longer wavelengths are more sensitive to bending loss and will allow light to exit out of the fiber core more than shorter wavelengths
Frage 15
Frage
What is the minimum separation of telecommunications cabling and electric motors & transformers
Antworten
-
12 inches
-
36 inches
-
48 inches
-
60 inches
Frage 16
Frage
This firestop material has the ability to absorb heat to prevent the temperature from rising on the other side of the fire barrier
Antworten
-
endothermic
-
ablative
-
intumescent
Frage 17
Frage
Where does the SCS begin
Antworten
-
where the SP terminates
-
ER
-
TR
Frage 18
Frage
What is the signal range for POTS
Antworten
-
300Hz-3400Hz
-
300MHz-3400MHz
-
20Hz-20,000Hz
Frage 19
Frage
This type of protector has a reaction time of 1-2 ns
Antworten
-
fire & data
-
carbon
-
gas
-
solid state
Frage 20
Frage
Cross-Connect Field Colors: Interbuilding Backbone
Frage 21
Frage
The frequency of CAT5e is
Antworten
-
100MHz
-
250MHz
-
500MHz
-
150MHz
Frage 22
Frage
The frequency of CAT3 is
Frage 23
Frage
The frequency of CAT6a is
Antworten
-
100MHz
-
250MHz
-
350MHz
-
500MHz
Frage 24
Frage
The frequency of CAT6 is
Antworten
-
100MHz
-
250MHz
-
350MHz
-
500MHz
Frage 25
Frage
How many pairs are in a super group
Frage 26
Frage
How many binder groups are in each super group
Frage 27
Frage
What are the 2 common methods of terminating balanced twisted pair cable (select all correct)
Frage 28
Frage
Which of the following cables meet the minimum requirements for cabling to a work area (select all correct)
Antworten
-
4 pair, 100 Ohm CAT5e cable
-
4 pair, 100 Ohm CAT6 cable
-
2 or more strands of 62.5 or 50 (OM1 or OM2)
-
2 or more strands of singlemode
Frage 29
Frage
Why is undercarpet cable not recommended (select all correct)
Frage 30
Frage
The interconnection between undercarpet cable and horizontal cable is called what
Antworten
-
TP (transition point)
-
CP (consolidation point)
-
MUTOA
Frage 31
Frage
If using undercarpet cable, what is recommended maximum length of the cable
Frage 32
Frage
What are the most common connectors for multimode fiber (select all correct)
Frage 33
Frage
What are the common modular connectors used in ITS (select all correct)
Frage 34
Frage
What are the most predominant coaxial cables (select all correct)
Antworten
-
Series 6
-
Series 59
-
Series 11
-
RG6
-
RG58
-
RG59
Frage 35
Frage
The F connector is the most commonly used connector for residential cable service
Frage 36
Frage
What are the common BNC connector types (select all correct)
Antworten
-
3 piece crimp
-
1 piece compression
-
screw-on
Frage 37
Frage
What is the maximum pulling tension of 4-pair, balanced twisted pair cabling
Antworten
-
25 pounds-force (lbf)
-
20 pounds-force (lbf)
-
30 pounds-force (lbf)
Frage 38
Frage
What is the minimum bend radius of 4 pair cable
Antworten
-
4 times cable diameter
-
5 times cable diameter
-
4 inches
-
5 inches
Frage 39
Frage
What is the recommended service slack for 4-pair cables at the work area
Antworten
-
12 inches
-
24 inches
-
36 inches
Frage 40
Frage
What is the recommended service slack for a 4 pair cable in the TR/ER
Frage 41
Frage
What is the recommended service slack for multipair cable in a TR/ER
Frage 42
Frage
What is the recommended service slack for 4 pair & multipair cable at a TE
Frage 43
Frage
The tensile strength of pull string is typically
Antworten
-
75-200 lbf
-
100-200 lbf
-
50-100 lbf
-
75-150 lbf
Frage 44
Frage
A pull string should be attached to cable with what type of knot and how many knots
Antworten
-
3 half hitches
-
2 half hitches
-
3 square knots
-
2 square knots
Frage 45
Frage
Structural steel members (red iron) can be used to support cables if they are spaced 4-5ft
Frage 46
Frage
What are the common splice connectors for copper (select all correct)
Antworten
-
straight through
-
butt splice
-
half tap
Frage 47
Frage
What are the common splice enclosures (select all correct)
Frage 48
Frage
Which copper splicing method allows the conductors to be folded into the splice and allows for maintenance, rearrangement and transfer of the conductors
Antworten
-
Inline
-
Foldback
-
Butt
-
Branch
Frage 49
Frage
What is the minimum bend radius of a 4 pair balanced twisted pair cord
Antworten
-
1x patch cord diameter
-
4x patch cord diameter
-
4 inches
-
2 inches
Frage 50
Frage
What is the minimum bend radius of a multipair cable
Frage 51
Frage
Cable pair twists for CAT3 must be maintained to within ____________ of termination
Antworten
-
3 inches
-
2 inches
-
1 inch
-
.5 inches
Frage 52
Frage
Cable pair twists for CAT5e or higher must be maintained to within ____________ of termination
Antworten
-
.5 inches
-
.25 inches
-
.75 inches
-
1 inch
Frage 53
Frage
110 blocks come in increments of ________ pairs (select all correct)
Frage 54
Frage
BIX blocks come in increments of ________ pairs (select all correct)
Frage 55
Frage
Field terminated patch cables are not recommended for CAT5e
Frage 56
Frage
What is the most common video connector in the industry
Frage 57
Frage
Specification and visual inspection is what phase of testing
Frage 58
Frage
Testing with various test equipment is what phase of testing
Frage 59
Frage
Documentation is what phase of testing
Frage 60
Frage
Except in particular cases, what is the maximum length of equipment cords
Frage 61
Frage
A consolidation point will extend the horizontal cabling length
Frage 62
Frage
What is the maximum amount of work areas that a MUTOA should serve
Frage 63
Frage
A minimum of 1 dedicated, non-switched duplex receptacle should be available for equipment in each _________
Frage 64
Frage
What is the maximum square footage a TE should serve
Frage 65
Frage
What is minimum recommended cable tray width for an ER, TR or EF
Antworten
-
12 inches
-
18 inches
-
6 inches
-
24 inches
Frage 66
Frage
Which grade of plywood has knotholes without any repair
Antworten
-
Grade A
-
Grade B
-
Grade C
-
Grade D
Frage 67
Frage
Which grade of plywood contains some blemishes and the occasional knothole
Antworten
-
Grade A
-
Grade B
-
Grade C
-
Grade D
Frage 68
Frage
Which grade of plywood has the knotholes cut out and replaced with a patch of clean wood
Antworten
-
Grade A
-
Grade B
-
Grade C
-
Grade D
Frage 69
Frage
Which grade of plywood is the highest grade and is without any surface blemishes
Antworten
-
Grade A
-
Grade B
-
Grade C
-
Grade D
Frage 70
Frage
Which grade of plywood should be used for ER, TR & EFs
Frage 71
Frage
How many walls should have plywood installed
Frage 72
Frage
Select all that apply to backboards in ERs, TRs & EFs
Antworten
-
3/4" thick plywood
-
at least 2 coats of fire retardant paint
-
minimum 1/4" toggle bolts
-
toggle bolts should be spaced 24 inches
-
toggle bolts should be 2 inches from the edge of the plywood
-
plywood should be mounted 6 inches AFF
Frage 73
Frage
Most ITS installations will require a 19 inch by 7 ft rack
Frage 74
Frage
What are the common depths of racks (select all correct)
Frage 75
Frage
What are the popular thread sizes for racks/cabinets (select all correct)
Frage 76
Frage
What is the preferred size of patch panels
Frage 77
Frage
What are the reasons that FMT is not recommended (select all correct)
Antworten
-
creep
-
shift
-
damage cable sheath
Frage 78
Frage
If using FMT, what rules must be followed (select all correct)
Frage 79
Frage
How many 90 degree bends are allowed in conduit segment
Frage 80
Frage
If more than two 90 degree bends are needed, what must be done (select all correct)
Antworten
-
run is not longer than 33ft
-
increase conduit 1 trade size
-
install one 90 degree bend within 12 inches of feed end
Frage 81
Frage
When conduits enter a TR through the floor, how far should they protrude
Antworten
-
6 inches
-
2-4 inches
-
1-3 inches
Frage 82
Frage
What are the 3 common depths of basket tray (rod stock tray) (select all correct)
Frage 83
Frage
This is the portion of the data center that actually houses the IT equipment
Antworten
-
Computer Room
-
Equipment Room
-
Entrance Room
Frage 84
Frage
Which types of cables are recognized in data center telecommunications (select all correct)
Frage 85
Frage
Which two types of coaxial cable does ANSI/TIA 942 recognize for E1, E3 & T3 circuits (select all correct)
Antworten
-
734-type
-
735-type
-
Series 6
-
Series 11
Frage 86
Frage
Which type of connectors are installed on 734-type and 735-type coaxial cable for E1, E3 & T3 circuits (select all correct)
Frage 87
Frage
Cable trays in data centers should be planned for initial maximum calculated fill ratio of ________%
Frage 88
Frage
How much clearance should be provided above the of cable trays when they are installed above cabinets
Antworten
-
12 inches
-
10 inches
-
6 inches
-
18 inches
Frage 89
Frage
How much clearance should be above a cable tray that is installed below a raised floor
Antworten
-
2 inches
-
3 inches
-
6 inches
-
12 inches
Frage 90
Frage
Cable trays installed under raised floors in data centers should be installed in the cold aisle
Frage 91
Frage
In a data center, how much horizontal cable management should be provided for each 1u of patch panel
Frage 92
Frage
Power strips supporting only single-corded equipment should be loaded no more than _______% of circuit capacity
Frage 93
Frage
Power strips supporting only dual-corded equipment should be loaded no more than _______% of circuit capacity
Frage 94
Frage
Some unique aspects of health care regarding access control are (select all correct)
Antworten
-
elevator controls (cab calls and override)
-
integration will infant protection, wandering patient and elopement systems
-
card readers not always being located at the door
-
multiple levels of access control for care providers, visitors and security
Frage 95
Frage
In a health care facility, PT (pneumatic tube) system is typically what size tubing
Frage 96
Frage
Central equipment cabinets are the heart of the system and likely will occupy 4ft x 8ft of wall space in the TR
Frage 97
Frage
HEPA/ultra-low penetration air (ULPA) vacuum cleaners shall trap _________% of particles 0.12 micrometers and larger
Frage 98
Frage
In health care facility projects, the safety officer or facilities director shall make at least _________ documented visit(s) per week to each construction work zone
Frage 99
Frage
This document is the understanding between the customer and the contractor
Antworten
-
project contract
-
scope of work
-
specifications
Frage 100
Frage
CLA Series System Drawings: Campus or Site Plans
Frage 101
Frage
CLA Series System Drawings: Layout of complete building per floor
Frage 102
Frage
CLA Series System Drawings: Serving Zones: drop locations and cable IDs
Frage 103
Frage
CLA Series System Drawings: Communication equipment rooms
Frage 104
Frage
CLA Series System Drawings: Typical detail drawings: face-plate labeling, firestopping
Frage 105
Frage
CLA Series System Drawings: Schedules
Frage 106
Frage
What are the 3 major areas in security that may be part of an ITS installer's work (select 3)
Frage 107
Frage
A fire alarm system should be designed by a licensed fire protection engineer to ensure proper coverage and code compliance
Frage 108
Frage
DAS consists of an infrastructure of electronic devices including (select all correct)
Antworten
-
amplifiers
-
cabling
-
connectors
-
antennas
-
hardware
Frage 109
Frage
This is a device that transmits and receives electromagnetic waves
Antworten
-
antenna
-
transmitter
-
transceiver
Frage 110
Frage
Each 6dB increase in an antenna equals the ___________ of the possible range
Frage 111
Frage
Each 6dB decrease in an antenna equals the ___________ of the possible antenna range
Frage 112
Frage
The standoffs for a radiating cable need to be _______ inches below the cable tray
Antworten
-
2 inches
-
3 inches
-
4 inches
-
6 inches
Frage 113
Frage
Wireless access points should be mounted at least ________ meter(s) from any metal obstructions
Frage 114
Frage
Most antennas used with APs indoors come with a ______ cable, commonly known as a pigtail
Frage 115
Frage
What are the 3 common voltages used in centrally amplified systems (select 3)
Frage 116
Frage
Which paging system operates at 24vdc
Frage 117
Frage
Which paging system will typically have 2 conductor cable installed
Antworten
-
centrally amplified
-
distributed amplified
Frage 118
Frage
What are the 2 common types of sound masking systems (select 2)
Antworten
-
in-plenum
-
direct-field
-
above ceiling
Frage 119
Frage
What time each day does the master clock send a longer pulse that corrects all of the secondary clocks to the correct hour
Frage 120
Frage
D-loading coils are commonly placed by telephone companies at which distance
Frage 121
Frage
H-loading coils are most commonly placed by the telephone company at which distance
Frage 122
Frage
Loss for premise cabling, including taps, should not exceed _____ dB of loss