Technician Review Questions Part 2

Beschreibung

Technician
eric rinehart
Quiz von eric rinehart, aktualisiert more than 1 year ago
eric rinehart
Erstellt von eric rinehart vor fast 9 Jahre
275
5

Zusammenfassung der Ressource

Frage 1

Frage
What is the recommended power range for microscopes to view the end face of an optical fiber connector
Antworten
  • 100x-200x
  • 100x-800x
  • 200x-400x

Frage 2

Frage
_____ cabling provides interconnection between TRs, ERs, main terminal space & EF (entrance facilities)
Antworten
  • backbone
  • horizontal
  • riser

Frage 3

Frage
To confine the light within the core by creating a reflective boundary is the purpose of the _______
Antworten
  • cladding
  • buffer
  • acrylate

Frage 4

Frage
This space is a special purpose room that provides and maintains a suitable operating environment for large telecommunications equipment
Antworten
  • ER
  • EF
  • TR
  • TE

Frage 5

Frage
During a retrofit, it is not required to remove all abandoned cable
Antworten
  • True
  • False

Frage 6

Frage
This space should not serve more than 3,600 sq/ft
Antworten
  • TE
  • TR
  • ER
  • EF

Frage 7

Frage
What is the most common specialty fastener used in ITS cabling
Antworten
  • j-hook
  • toggle bolt
  • drive ring
  • bridal ring

Frage 8

Frage
Interbuilding circuits are considered to have lightning exposure unless 1 or more conditions exist (select all correct)
Antworten
  • Buildings close together and sufficiently high
  • Cable run is 140ft or less (underground or in conduit)
  • Area having an avg. of 5 or fewer t-storms per year and earth resistivity less than 100 ohms

Frage 9

Frage
This tester uses Rayleigh scattering & Fresnal reflection to measure the characteristics of an optical fiber
Antworten
  • OTDR
  • OLTS
  • VFL

Frage 10

Frage
The ITS installer is allowed to add more firestopping product to get a higher rating
Antworten
  • True
  • False

Frage 11

Frage
Cross-Connect Field Colors: Future (Key Telephone Systems)
Antworten
  • Red
  • Yellow
  • Gray
  • Purple

Frage 12

Frage
What is used to flush electrolyte burns to the skin
Antworten
  • water
  • milk
  • sodium bicarbonate

Frage 13

Frage
Shorter wavelengths of light exhibit greater amounts of attenuation because of Rayleigh scattering
Antworten
  • True
  • False

Frage 14

Frage
Longer wavelengths are more sensitive to bending loss and will allow light to exit out of the fiber core more than shorter wavelengths
Antworten
  • True
  • False

Frage 15

Frage
What is the minimum separation of telecommunications cabling and electric motors & transformers
Antworten
  • 12 inches
  • 36 inches
  • 48 inches
  • 60 inches

Frage 16

Frage
This firestop material has the ability to absorb heat to prevent the temperature from rising on the other side of the fire barrier
Antworten
  • endothermic
  • ablative
  • intumescent

Frage 17

Frage
Where does the SCS begin
Antworten
  • where the SP terminates
  • ER
  • TR

Frage 18

Frage
What is the signal range for POTS
Antworten
  • 300Hz-3400Hz
  • 300MHz-3400MHz
  • 20Hz-20,000Hz

Frage 19

Frage
This type of protector has a reaction time of 1-2 ns
Antworten
  • fire & data
  • carbon
  • gas
  • solid state

Frage 20

Frage
Cross-Connect Field Colors: Interbuilding Backbone
Antworten
  • brown
  • gray
  • white
  • purple

Frage 21

Frage
The frequency of CAT5e is
Antworten
  • 100MHz
  • 250MHz
  • 500MHz
  • 150MHz

Frage 22

Frage
The frequency of CAT3 is
Antworten
  • 16MHz
  • 20MHz
  • 50MHz
  • 100MHz

Frage 23

Frage
The frequency of CAT6a is
Antworten
  • 100MHz
  • 250MHz
  • 350MHz
  • 500MHz

Frage 24

Frage
The frequency of CAT6 is
Antworten
  • 100MHz
  • 250MHz
  • 350MHz
  • 500MHz

Frage 25

Frage
How many pairs are in a super group
Antworten
  • 600
  • 100
  • 400
  • 300

Frage 26

Frage
How many binder groups are in each super group
Antworten
  • 12
  • 24
  • 50
  • 25

Frage 27

Frage
What are the 2 common methods of terminating balanced twisted pair cable (select all correct)
Antworten
  • IDC
  • IPC
  • RJ45
  • Punch Down

Frage 28

Frage
Which of the following cables meet the minimum requirements for cabling to a work area (select all correct)
Antworten
  • 4 pair, 100 Ohm CAT5e cable
  • 4 pair, 100 Ohm CAT6 cable
  • 2 or more strands of 62.5 or 50 (OM1 or OM2)
  • 2 or more strands of singlemode

Frage 29

Frage
Why is undercarpet cable not recommended (select all correct)
Antworten
  • susceptibility to damage
  • limited flexibility for moves, adds or changes (MACs)
  • poor cable performance
  • damages carpet

Frage 30

Frage
The interconnection between undercarpet cable and horizontal cable is called what
Antworten
  • TP (transition point)
  • CP (consolidation point)
  • MUTOA

Frage 31

Frage
If using undercarpet cable, what is recommended maximum length of the cable
Antworten
  • 33ft
  • 50ft
  • 20ft
  • 100ft

Frage 32

Frage
What are the most common connectors for multimode fiber (select all correct)
Antworten
  • ST
  • SC
  • LC

Frage 33

Frage
What are the common modular connectors used in ITS (select all correct)
Antworten
  • 4P4C
  • 6P6C
  • 8P8C
  • RJ45

Frage 34

Frage
What are the most predominant coaxial cables (select all correct)
Antworten
  • Series 6
  • Series 59
  • Series 11
  • RG6
  • RG58
  • RG59

Frage 35

Frage
The F connector is the most commonly used connector for residential cable service
Antworten
  • True
  • False

Frage 36

Frage
What are the common BNC connector types (select all correct)
Antworten
  • 3 piece crimp
  • 1 piece compression
  • screw-on

Frage 37

Frage
What is the maximum pulling tension of 4-pair, balanced twisted pair cabling
Antworten
  • 25 pounds-force (lbf)
  • 20 pounds-force (lbf)
  • 30 pounds-force (lbf)

Frage 38

Frage
What is the minimum bend radius of 4 pair cable
Antworten
  • 4 times cable diameter
  • 5 times cable diameter
  • 4 inches
  • 5 inches

Frage 39

Frage
What is the recommended service slack for 4-pair cables at the work area
Antworten
  • 12 inches
  • 24 inches
  • 36 inches

Frage 40

Frage
What is the recommended service slack for a 4 pair cable in the TR/ER
Antworten
  • farthest corner of room plus floor to ceiling
  • length of backboard plus floor to ceiling
  • 15 feet
  • 10 feet

Frage 41

Frage
What is the recommended service slack for multipair cable in a TR/ER
Antworten
  • length of backboard plus floor to ceiling
  • farthest corner plus floor to ceiling
  • 15 feet
  • 20 feet

Frage 42

Frage
What is the recommended service slack for 4 pair & multipair cable at a TE
Antworten
  • 10ft
  • 15ft
  • 6.6ft

Frage 43

Frage
The tensile strength of pull string is typically
Antworten
  • 75-200 lbf
  • 100-200 lbf
  • 50-100 lbf
  • 75-150 lbf

Frage 44

Frage
A pull string should be attached to cable with what type of knot and how many knots
Antworten
  • 3 half hitches
  • 2 half hitches
  • 3 square knots
  • 2 square knots

Frage 45

Frage
Structural steel members (red iron) can be used to support cables if they are spaced 4-5ft
Antworten
  • True
  • False

Frage 46

Frage
What are the common splice connectors for copper (select all correct)
Antworten
  • straight through
  • butt splice
  • half tap

Frage 47

Frage
What are the common splice enclosures (select all correct)
Antworten
  • straight
  • butt
  • branch

Frage 48

Frage
Which copper splicing method allows the conductors to be folded into the splice and allows for maintenance, rearrangement and transfer of the conductors
Antworten
  • Inline
  • Foldback
  • Butt
  • Branch

Frage 49

Frage
What is the minimum bend radius of a 4 pair balanced twisted pair cord
Antworten
  • 1x patch cord diameter
  • 4x patch cord diameter
  • 4 inches
  • 2 inches

Frage 50

Frage
What is the minimum bend radius of a multipair cable
Antworten
  • follow manufacturer specifications
  • 10x diameter of cable
  • 15x diameter of cable

Frage 51

Frage
Cable pair twists for CAT3 must be maintained to within ____________ of termination
Antworten
  • 3 inches
  • 2 inches
  • 1 inch
  • .5 inches

Frage 52

Frage
Cable pair twists for CAT5e or higher must be maintained to within ____________ of termination
Antworten
  • .5 inches
  • .25 inches
  • .75 inches
  • 1 inch

Frage 53

Frage
110 blocks come in increments of ________ pairs (select all correct)
Antworten
  • 50
  • 100
  • 300
  • 900
  • 600

Frage 54

Frage
BIX blocks come in increments of ________ pairs (select all correct)
Antworten
  • 50
  • 250
  • 300
  • 900
  • 100

Frage 55

Frage
Field terminated patch cables are not recommended for CAT5e
Antworten
  • True
  • False

Frage 56

Frage
What is the most common video connector in the industry
Antworten
  • F
  • BNC
  • N
  • HDMI

Frage 57

Frage
Specification and visual inspection is what phase of testing
Antworten
  • Phase 1
  • Phase 2
  • Phase 3

Frage 58

Frage
Testing with various test equipment is what phase of testing
Antworten
  • Phase 1
  • Phase 2
  • Phase 3

Frage 59

Frage
Documentation is what phase of testing
Antworten
  • Phase 1
  • Phase 2
  • Phase 3

Frage 60

Frage
Except in particular cases, what is the maximum length of equipment cords
Antworten
  • 16.5ft
  • 5ft
  • 10ft

Frage 61

Frage
A consolidation point will extend the horizontal cabling length
Antworten
  • True
  • False

Frage 62

Frage
What is the maximum amount of work areas that a MUTOA should serve
Antworten
  • 12
  • 24
  • 10
  • 20

Frage 63

Frage
A minimum of 1 dedicated, non-switched duplex receptacle should be available for equipment in each _________
Antworten
  • TE
  • TR
  • ER
  • EF

Frage 64

Frage
What is the maximum square footage a TE should serve
Antworten
  • 3600
  • 5000
  • 2400
  • 4000

Frage 65

Frage
What is minimum recommended cable tray width for an ER, TR or EF
Antworten
  • 12 inches
  • 18 inches
  • 6 inches
  • 24 inches

Frage 66

Frage
Which grade of plywood has knotholes without any repair
Antworten
  • Grade A
  • Grade B
  • Grade C
  • Grade D

Frage 67

Frage
Which grade of plywood contains some blemishes and the occasional knothole
Antworten
  • Grade A
  • Grade B
  • Grade C
  • Grade D

Frage 68

Frage
Which grade of plywood has the knotholes cut out and replaced with a patch of clean wood
Antworten
  • Grade A
  • Grade B
  • Grade C
  • Grade D

Frage 69

Frage
Which grade of plywood is the highest grade and is without any surface blemishes
Antworten
  • Grade A
  • Grade B
  • Grade C
  • Grade D

Frage 70

Frage
Which grade of plywood should be used for ER, TR & EFs
Antworten
  • A/C
  • A/B
  • A/A
  • A/D

Frage 71

Frage
How many walls should have plywood installed
Antworten
  • 2
  • 3
  • 4

Frage 72

Frage
Select all that apply to backboards in ERs, TRs & EFs
Antworten
  • 3/4" thick plywood
  • at least 2 coats of fire retardant paint
  • minimum 1/4" toggle bolts
  • toggle bolts should be spaced 24 inches
  • toggle bolts should be 2 inches from the edge of the plywood
  • plywood should be mounted 6 inches AFF

Frage 73

Frage
Most ITS installations will require a 19 inch by 7 ft rack
Antworten
  • True
  • False

Frage 74

Frage
What are the common depths of racks (select all correct)
Antworten
  • 4 inch
  • 6 inch
  • 8 inch

Frage 75

Frage
What are the popular thread sizes for racks/cabinets (select all correct)
Antworten
  • M5
  • M6
  • 10-32
  • 12-24

Frage 76

Frage
What is the preferred size of patch panels
Antworten
  • 48 port
  • 24 port
  • 2u
  • 1u

Frage 77

Frage
What are the reasons that FMT is not recommended (select all correct)
Antworten
  • creep
  • shift
  • damage cable sheath

Frage 78

Frage
If using FMT, what rules must be followed (select all correct)
Antworten
  • up 1 trade size
  • limit to 20ft
  • no more than two 90 degree bends

Frage 79

Frage
How many 90 degree bends are allowed in conduit segment
Antworten
  • 2
  • 3
  • 4

Frage 80

Frage
If more than two 90 degree bends are needed, what must be done (select all correct)
Antworten
  • run is not longer than 33ft
  • increase conduit 1 trade size
  • install one 90 degree bend within 12 inches of feed end

Frage 81

Frage
When conduits enter a TR through the floor, how far should they protrude
Antworten
  • 6 inches
  • 2-4 inches
  • 1-3 inches

Frage 82

Frage
What are the 3 common depths of basket tray (rod stock tray) (select all correct)
Antworten
  • 1
  • 2
  • 4
  • 6

Frage 83

Frage
This is the portion of the data center that actually houses the IT equipment
Antworten
  • Computer Room
  • Equipment Room
  • Entrance Room

Frage 84

Frage
Which types of cables are recognized in data center telecommunications (select all correct)
Antworten
  • 100 ohm balanced twisted pair
  • multimode fiber
  • singlemode fiber
  • 50/75 ohm coaxial

Frage 85

Frage
Which two types of coaxial cable does ANSI/TIA 942 recognize for E1, E3 & T3 circuits (select all correct)
Antworten
  • 734-type
  • 735-type
  • Series 6
  • Series 11

Frage 86

Frage
Which type of connectors are installed on 734-type and 735-type coaxial cable for E1, E3 & T3 circuits (select all correct)
Antworten
  • BNC
  • TNC
  • F
  • N

Frage 87

Frage
Cable trays in data centers should be planned for initial maximum calculated fill ratio of ________%
Antworten
  • 25%
  • 40%
  • 50%
  • 30%

Frage 88

Frage
How much clearance should be provided above the of cable trays when they are installed above cabinets
Antworten
  • 12 inches
  • 10 inches
  • 6 inches
  • 18 inches

Frage 89

Frage
How much clearance should be above a cable tray that is installed below a raised floor
Antworten
  • 2 inches
  • 3 inches
  • 6 inches
  • 12 inches

Frage 90

Frage
Cable trays installed under raised floors in data centers should be installed in the cold aisle
Antworten
  • True
  • False

Frage 91

Frage
In a data center, how much horizontal cable management should be provided for each 1u of patch panel
Antworten
  • 1u
  • 2u
  • 3u

Frage 92

Frage
Power strips supporting only single-corded equipment should be loaded no more than _______% of circuit capacity
Antworten
  • 80%
  • 60%
  • 50%
  • 75%

Frage 93

Frage
Power strips supporting only dual-corded equipment should be loaded no more than _______% of circuit capacity
Antworten
  • 40%
  • 80%
  • 60%
  • 75%

Frage 94

Frage
Some unique aspects of health care regarding access control are (select all correct)
Antworten
  • elevator controls (cab calls and override)
  • integration will infant protection, wandering patient and elopement systems
  • card readers not always being located at the door
  • multiple levels of access control for care providers, visitors and security

Frage 95

Frage
In a health care facility, PT (pneumatic tube) system is typically what size tubing
Antworten
  • 4 inch
  • 6 inch
  • 8 inch

Frage 96

Frage
Central equipment cabinets are the heart of the system and likely will occupy 4ft x 8ft of wall space in the TR
Antworten
  • True
  • False

Frage 97

Frage
HEPA/ultra-low penetration air (ULPA) vacuum cleaners shall trap _________% of particles 0.12 micrometers and larger
Antworten
  • 99.999
  • 98.999
  • 99.899

Frage 98

Frage
In health care facility projects, the safety officer or facilities director shall make at least _________ documented visit(s) per week to each construction work zone
Antworten
  • 1
  • 2
  • 3

Frage 99

Frage
This document is the understanding between the customer and the contractor
Antworten
  • project contract
  • scope of work
  • specifications

Frage 100

Frage
CLA Series System Drawings: Campus or Site Plans
Antworten
  • T0
  • T1
  • T2
  • T3

Frage 101

Frage
CLA Series System Drawings: Layout of complete building per floor
Antworten
  • T0
  • T1
  • T2
  • T3

Frage 102

Frage
CLA Series System Drawings: Serving Zones: drop locations and cable IDs
Antworten
  • T2
  • T3
  • T4
  • T5

Frage 103

Frage
CLA Series System Drawings: Communication equipment rooms
Antworten
  • T2
  • T3
  • T4
  • T5

Frage 104

Frage
CLA Series System Drawings: Typical detail drawings: face-plate labeling, firestopping
Antworten
  • T2
  • T3
  • T4
  • T5

Frage 105

Frage
CLA Series System Drawings: Schedules
Antworten
  • T1
  • T0
  • T4
  • T5

Frage 106

Frage
What are the 3 major areas in security that may be part of an ITS installer's work (select 3)
Antworten
  • Intrusion detection system
  • access control system
  • video surveillance
  • patient monitoring

Frage 107

Frage
A fire alarm system should be designed by a licensed fire protection engineer to ensure proper coverage and code compliance
Antworten
  • True
  • False

Frage 108

Frage
DAS consists of an infrastructure of electronic devices including (select all correct)
Antworten
  • amplifiers
  • cabling
  • connectors
  • antennas
  • hardware

Frage 109

Frage
This is a device that transmits and receives electromagnetic waves
Antworten
  • antenna
  • transmitter
  • transceiver

Frage 110

Frage
Each 6dB increase in an antenna equals the ___________ of the possible range
Antworten
  • doubling
  • halving

Frage 111

Frage
Each 6dB decrease in an antenna equals the ___________ of the possible antenna range
Antworten
  • doubling
  • halving

Frage 112

Frage
The standoffs for a radiating cable need to be _______ inches below the cable tray
Antworten
  • 2 inches
  • 3 inches
  • 4 inches
  • 6 inches

Frage 113

Frage
Wireless access points should be mounted at least ________ meter(s) from any metal obstructions
Antworten
  • 1 meter
  • 2 meters

Frage 114

Frage
Most antennas used with APs indoors come with a ______ cable, commonly known as a pigtail
Antworten
  • 3ft
  • 2ft
  • 1.5ft

Frage 115

Frage
What are the 3 common voltages used in centrally amplified systems (select 3)
Antworten
  • 25v
  • 70v
  • 100v
  • 48v

Frage 116

Frage
Which paging system operates at 24vdc
Antworten
  • centrally amplified
  • distributed amplifier system

Frage 117

Frage
Which paging system will typically have 2 conductor cable installed
Antworten
  • centrally amplified
  • distributed amplified

Frage 118

Frage
What are the 2 common types of sound masking systems (select 2)
Antworten
  • in-plenum
  • direct-field
  • above ceiling

Frage 119

Frage
What time each day does the master clock send a longer pulse that corrects all of the secondary clocks to the correct hour
Antworten
  • 6pm
  • 12pm
  • 12am
  • 9pm

Frage 120

Frage
D-loading coils are commonly placed by telephone companies at which distance
Antworten
  • 1.37km
  • 1.8km
  • 1.5km

Frage 121

Frage
H-loading coils are most commonly placed by the telephone company at which distance
Antworten
  • 1.37km
  • 1.5km
  • 1.8km

Frage 122

Frage
Loss for premise cabling, including taps, should not exceed _____ dB of loss
Antworten
  • 7-8
  • 7-9
  • 8-9
  • 7-10
Zusammenfassung anzeigen Zusammenfassung ausblenden

ähnlicher Inhalt

Chapter 4 Bonding Part 1
eric rinehart
Chapter 2 Safety
eric rinehart
Chapter 1 Transmission
eric rinehart
Chapter 7 Firestopping
eric rinehart
8 Bonding and Grounding
Jeanie Fitzgerald
Chapter 6 Fiber
eric rinehart
8 Bonding and Grounding 1
Jeanie Fitzgerald
8 Bonding and Grounding
Jeanie Fitzgerald
Telecomms Rigging
peter.roberts