2 SCS spaces and pathways

Beschreibung

Class quiz (Class Quiz) Quiz am 2 SCS spaces and pathways, erstellt von Jeanie Fitzgerald am 19/07/2017.
Jeanie Fitzgerald
Quiz von Jeanie Fitzgerald, aktualisiert more than 1 year ago
Jeanie Fitzgerald
Erstellt von Jeanie Fitzgerald vor fast 7 Jahre
108
2

Zusammenfassung der Ressource

Frage 1

Frage
Entrance facilities may include ( select all that apply)
Antworten
  • Entrance point to the building envelope
  • Demarcation point for SP and customer premise cabling
  • Primary surge protection devices
  • Transistion hardware

Frage 2

Frage
Where electrical and building codes apply, only listed cables can be used within a building structure except for an entrance cable that is transitioned or terminated. What is this rule referred to as.
Antworten
  • 25 ft rule
  • 50 ft rule
  • 100 ft rule

Frage 3

Frage
There are multiple types of entrances to Entrance facility. Which is economical over the life cycle, preserves aesthetics, and provides security and physical protection.
Antworten
  • Underground
  • Buried
  • Ariel
  • Tunnel

Frage 4

Frage
Which of the following preserves the aesthetic appearance, has low initial cost, but is inflexible to future service reinforcement or changes and requires a sleeve or conduit to enter the building.
Antworten
  • Underground
  • Buried
  • Tunnel
  • Aerial

Frage 5

Frage
Which of the following applies to Aerial entrance to entrance facility
Antworten
  • Provides low installation cost
  • Subject to traffic and pedestrian clearances
  • Does not affect aesthetics
  • Susceptible to environmental conditions ( ice loading, tree limbs, winds, lightning)

Frage 6

Frage
In wireless entrance using an existing equipment room, the WSP (wireless service provider) typically provides connection through existing SP (service provider) cabling.
Antworten
  • True
  • False

Frage 7

Frage
Wireless entrance may use media converters to convert __________ ____________from the antenna to __________ ___________ and into the DAS.
Antworten
  • building/campus, interface/demarcation
  • copper cabling/optical fiber
  • service entrance/connecting hardware

Frage 8

Frage
An Equipment room generally houses equipment that...
Antworten
  • Serves one floor of a building or portion of a floor
  • Serves an entire building, campus or customer
  • serves a dedicated local group of users

Frage 9

Frage
Which of the following is considered to be floor serving as opposed to building serving
Antworten
  • Entrance facility
  • Telecommunication room
  • Equipment room
  • Telecommunication enclosure

Frage 10

Frage
Which of the following serves as a point of termination for horizontal and backbone cables on compatible connecting hardware
Antworten
  • ER
  • EF
  • TR
  • TE

Frage 11

Frage
A telecommunication enclosure may be used in place of a telecommunication room.
Antworten
  • True
  • False

Frage 12

Frage
Telecommunications pathways permit the placement of_______________and ______________ ____________that support the structured cabling system (SCS)
Antworten
  • plenum and underfloor cable
  • equipment and patch cables
  • horizontal and backbone cables

Frage 13

Frage
While the local AHJ may allow its use, BICSI recommends that ______________ not be used inside commercial buildings.
Antworten
  • ENT electrical non metallic tubing
  • FMT flexible metallic tubing
  • PVC polyvinyl chloride conduit

Frage 14

Frage
Which of the following should never be used for telecommunications cabling.
Antworten
  • FMT
  • FMC
  • RMC

Frage 15

Frage
Fill ratio for new installation of conduit is ____% while the maximum fill ratio is ____%
Antworten
  • 30%, 50%
  • 40%, 60%
  • 50%, 80%

Frage 16

Frage
Following fill ratio for firestoppng is critical since an _________________conduit cannot be effectively firestopped
Antworten
  • overfilled
  • partially filled
  • empty

Frage 17

Frage
A stub up conduit terminates in a _______________ orientation while a stub out terminates in a _________________ orientation.
Antworten
  • vertical/horizontal
  • horizontal/vertical

Frage 18

Frage
Cable trays and runways are commonly provided a minimum of ____ in. clearance above the pathway and do not contain more than ___ in. depth of cable.
Antworten
  • 12, 6
  • 6, 6
  • 3, 6

Frage 19

Frage
A tubular stock ladder rack is manufactured with a depth of 1.5 and the width varies from 6 in. to 48 in.
Antworten
  • True
  • False

Frage 20

Frage
Wire basket cable trays are available in three depths, choose all that apply
Antworten
  • 2 in.
  • 4 in.
  • 6 in.
  • 8 in.

Frage 21

Frage
Open top cable supports are available in sizes for larger quantities of cable but are typically intended to support up to 50 cables between tray and work area.
Antworten
  • True
  • False

Frage 22

Frage
A _____ covers an area generally associated with some or all of the space within a building. Workspace devices are connected to a centralized device ( switch or server)
Antworten
  • WAN /wireless area network
  • CAN /campus area network
  • LAN /local area network

Frage 23

Frage
A _________ area network is created by linking two or more buildings that are in close proximity to each other.
Antworten
  • CAN
  • LAN
  • WAN

Frage 24

Frage
This is a device that manages one or more resources shared by workstation users and administrators on a network.
Antworten
  • Switch
  • Server
  • Router

Frage 25

Frage
This is a network access device that provides a centralized point for LAN communications.
Antworten
  • Server
  • Switch
  • Router

Frage 26

Frage
This device makes it possible to segment an organizational network into multiple broadcast domains, also referred to as subnets and or subnetworks.
Antworten
  • server
  • switch
  • router

Frage 27

Frage
For Data Centers, to aid in design, levels of redundancy have been established. These are listed as a class (0-4). Which ANSI/BICSI publication would cover this.
Antworten
  • ANSI/BICSI 001-2009
  • ANSI/BICSI 002-2014
  • ANSI/BICSI 003-2014

Frage 28

Frage
Data centers may have multiple entrance rooms for redundancy, and the entrance room is typically located outside the computer room.
Antworten
  • True
  • False

Frage 29

Frage
The computer room is the core of the data center. While it can be equated to the equipment room, there are several significant differences. Select all that apply
Antworten
  • Cabinets and quantities ( multiple rows of multiple cabinets bolted together)
  • Cable density, (quantities of cables per cabinet can be up to 200 )
  • Bonding and grounding (may be installed and managed by electrical personnel)
  • UPS ( typically managed by electrical personnel)

Frage 30

Frage
Data centers have special regulations and rules that must be followed including security , work to be performed , safety, access, etc. Failure to comply will result in removal from the premises.
Antworten
  • True
  • False
Zusammenfassung anzeigen Zusammenfassung ausblenden

ähnlicher Inhalt

Zeiten Englisch
Janine Egli
10 Lernmethoden
Laura Overhoff
Englisch Lernwortschatz A1-C1 Teil 2
Chiara Braun
SL2
N H
Vetie Radiologie VL-Fragen
Carolina Heide
Vetie Radiologie VL WS 11/12
Cedric-Bo Lüpkemann
Jour Gesko WS 18/19
Adrienne Tschaudi
Vetie Para Morphologie Helminthen
Kristin E
Vetie Reprospaß
Tropsi B
Vetie - Allgemeine Pathologie 21
Till S
Vetie Berufsrecht 2019
Mascha K.