The frequency of CAT5e is
100MHz
250MHz
500MHz
150MHz
The frequency of CAT3 is
16MHz
20MHz
50MHz
The frequency of CAT6a is
350MHz
The frequency of CAT6 is
How many pairs are in a super group
600
100
400
300
How many binder groups are in each super group
12
24
50
25
What are the 2 common methods of terminating balanced twisted pair cable (select all correct)
IDC
IPC
RJ45
Punch Down
Which of the following cables meet the minimum requirements for cabling to a work area (select all correct)
4 pair, 100 Ohm CAT5e cable
4 pair, 100 Ohm CAT6 cable
2 or more strands of 62.5 or 50 (OM1 or OM2)
2 or more strands of singlemode
Why is undercarpet cable not recommended (select all correct)
susceptibility to damage
limited flexibility for moves, adds or changes (MACs)
poor cable performance
damages carpet
The interconnection between undercarpet cable and horizontal cable is called what
TP (transition point)
CP (consolidation point)
MUTOA
If using undercarpet cable, what is recommended maximum length of the cable
33ft
50ft
20ft
100ft
What are the common modular connectors used in ITS (select all correct)
4P4C
6P6C
8P8C
What are the most predominant coaxial cables (select all correct)
Series 6
Series 59
Series 11
RG6
RG58
RG59
The F connector is the most commonly used connector for residential cable service
What are the common BNC connector types (select all correct)
3 piece crimp
1 piece compression
screw-on
What is the maximum pulling tension of 4-pair, balanced twisted pair cabling
25 pounds-force (lbf)
20 pounds-force (lbf)
30 pounds-force (lbf)
What is the minimum bend radius of 4 pair cable
4 times cable diameter
5 times cable diameter
4 inches
5 inches
What is the recommended service slack for 4-pair cables at the work area
12 inches
24 inches
36 inches
What is the recommended service slack for a 4 pair cable in the TR/ER
farthest corner of room plus floor to ceiling
length of backboard plus floor to ceiling
15 feet
10 feet
What is the recommended service slack for multipair cable in a TR/ER
farthest corner plus floor to ceiling
20 feet
What is the recommended service slack for 4 pair & multipair cable at a TE
10ft
15ft
6.6ft
The tensile strength of pull string is typically
75-200 lbf
100-200 lbf
50-100 lbf
75-150 lbf
A pull string should be attached to cable with what type of knot and how many knots
3 half hitches
2 half hitches
3 square knots
2 square knots
Structural steel members (red iron) can be used to support cables if they are spaced 4-5ft
What are the common splice connectors for copper (select all correct)
straight through
butt splice
half tap
What are the common splice enclosures (select all correct)
straight
butt
branch
Which copper splicing method allows the conductors to be folded into the splice and allows for maintenance, rearrangement and transfer of the conductors
Inline
Foldback
Butt
Branch
What is the minimum bend radius of a 4 pair balanced twisted pair cord
1x patch cord diameter
4x patch cord diameter
2 inches
What is the minimum bend radius of a multipair cable
follow manufacturer specifications
10x diameter of cable
15x diameter of cable
Cable pair twists for CAT3 must be maintained to within ____________ of termination
3 inches
1 inch
.5 inches
Cable pair twists for CAT5e or higher must be maintained to within ____________ of termination
.25 inches
.75 inches
110 blocks come in increments of ________ pairs (select all correct)
900
BIX blocks come in increments of ________ pairs (select all correct)
250
Field terminated patch cables are not recommended for CAT5e
What is the most common video connector in the industry
F
BNC
N
HDMI
Specification and visual inspection is what phase of testing
Phase 1
Phase 2
Phase 3
Testing with various test equipment is what phase of testing
Documentation is what phase of testing