Pregunta 1
Pregunta
What is the recommended power range for microscopes to view the end face of an optical fiber connector
Respuesta
-
100x-200x
-
100x-800x
-
200x-400x
Pregunta 2
Pregunta
_____ cabling provides interconnection between TRs, ERs, main terminal space & EF (entrance facilities)
Respuesta
-
backbone
-
horizontal
-
riser
Pregunta 3
Pregunta
To confine the light within the core by creating a reflective boundary is the purpose of the _______
Pregunta 4
Pregunta
This space is a special purpose room that provides and maintains a suitable operating environment for large telecommunications equipment
Pregunta 5
Pregunta
During a retrofit, it is not required to remove all abandoned cable
Pregunta 6
Pregunta
This space should not serve more than 3,600 sq/ft
Pregunta 7
Pregunta
What is the most common specialty fastener used in ITS cabling
Respuesta
-
j-hook
-
toggle bolt
-
drive ring
-
bridal ring
Pregunta 8
Pregunta
Interbuilding circuits are considered to have lightning exposure unless 1 or more conditions exist (select all correct)
Respuesta
-
Buildings close together and sufficiently high
-
Cable run is 140ft or less (underground or in conduit)
-
Area having an avg. of 5 or fewer t-storms per year and earth resistivity less than 100 ohms
Pregunta 9
Pregunta
This tester uses Rayleigh scattering & Fresnal reflection to measure the characteristics of an optical fiber
Pregunta 10
Pregunta
The ITS installer is allowed to add more firestopping product to get a higher rating
Pregunta 11
Pregunta
Cross-Connect Field Colors: Future (Key Telephone Systems)
Pregunta 12
Pregunta
What is used to flush electrolyte burns to the skin
Respuesta
-
water
-
milk
-
sodium bicarbonate
Pregunta 13
Pregunta
Shorter wavelengths of light exhibit greater amounts of attenuation because of Rayleigh scattering
Pregunta 14
Pregunta
Longer wavelengths are more sensitive to bending loss and will allow light to exit out of the fiber core more than shorter wavelengths
Pregunta 15
Pregunta
What is the minimum separation of telecommunications cabling and electric motors & transformers
Respuesta
-
12 inches
-
36 inches
-
48 inches
-
60 inches
Pregunta 16
Pregunta
This firestop material has the ability to absorb heat to prevent the temperature from rising on the other side of the fire barrier
Respuesta
-
endothermic
-
ablative
-
intumescent
Pregunta 17
Pregunta
Where does the SCS begin
Respuesta
-
where the SP terminates
-
ER
-
TR
Pregunta 18
Pregunta
What is the signal range for POTS
Respuesta
-
300Hz-3400Hz
-
300MHz-3400MHz
-
20Hz-20,000Hz
Pregunta 19
Pregunta
This type of protector has a reaction time of 1-2 ns
Respuesta
-
fire & data
-
carbon
-
gas
-
solid state
Pregunta 20
Pregunta
Cross-Connect Field Colors: Interbuilding Backbone
Pregunta 21
Pregunta
The frequency of CAT5e is
Respuesta
-
100MHz
-
250MHz
-
500MHz
-
150MHz
Pregunta 22
Pregunta
The frequency of CAT3 is
Pregunta 23
Pregunta
The frequency of CAT6a is
Respuesta
-
100MHz
-
250MHz
-
350MHz
-
500MHz
Pregunta 24
Pregunta
The frequency of CAT6 is
Respuesta
-
100MHz
-
250MHz
-
350MHz
-
500MHz
Pregunta 25
Pregunta
How many pairs are in a super group
Pregunta 26
Pregunta
How many binder groups are in each super group
Pregunta 27
Pregunta
What are the 2 common methods of terminating balanced twisted pair cable (select all correct)
Pregunta 28
Pregunta
Which of the following cables meet the minimum requirements for cabling to a work area (select all correct)
Respuesta
-
4 pair, 100 Ohm CAT5e cable
-
4 pair, 100 Ohm CAT6 cable
-
2 or more strands of 62.5 or 50 (OM1 or OM2)
-
2 or more strands of singlemode
Pregunta 29
Pregunta
Why is undercarpet cable not recommended (select all correct)
Pregunta 30
Pregunta
The interconnection between undercarpet cable and horizontal cable is called what
Respuesta
-
TP (transition point)
-
CP (consolidation point)
-
MUTOA
Pregunta 31
Pregunta
If using undercarpet cable, what is recommended maximum length of the cable
Pregunta 32
Pregunta
What are the most common connectors for multimode fiber (select all correct)
Pregunta 33
Pregunta
What are the common modular connectors used in ITS (select all correct)
Pregunta 34
Pregunta
What are the most predominant coaxial cables (select all correct)
Respuesta
-
Series 6
-
Series 59
-
Series 11
-
RG6
-
RG58
-
RG59
Pregunta 35
Pregunta
The F connector is the most commonly used connector for residential cable service
Pregunta 36
Pregunta
What are the common BNC connector types (select all correct)
Respuesta
-
3 piece crimp
-
1 piece compression
-
screw-on
Pregunta 37
Pregunta
What is the maximum pulling tension of 4-pair, balanced twisted pair cabling
Respuesta
-
25 pounds-force (lbf)
-
20 pounds-force (lbf)
-
30 pounds-force (lbf)
Pregunta 38
Pregunta
What is the minimum bend radius of 4 pair cable
Respuesta
-
4 times cable diameter
-
5 times cable diameter
-
4 inches
-
5 inches
Pregunta 39
Pregunta
What is the recommended service slack for 4-pair cables at the work area
Respuesta
-
12 inches
-
24 inches
-
36 inches
Pregunta 40
Pregunta
What is the recommended service slack for a 4 pair cable in the TR/ER
Pregunta 41
Pregunta
What is the recommended service slack for multipair cable in a TR/ER
Pregunta 42
Pregunta
What is the recommended service slack for 4 pair & multipair cable at a TE
Pregunta 43
Pregunta
The tensile strength of pull string is typically
Respuesta
-
75-200 lbf
-
100-200 lbf
-
50-100 lbf
-
75-150 lbf
Pregunta 44
Pregunta
A pull string should be attached to cable with what type of knot and how many knots
Respuesta
-
3 half hitches
-
2 half hitches
-
3 square knots
-
2 square knots
Pregunta 45
Pregunta
Structural steel members (red iron) can be used to support cables if they are spaced 4-5ft
Pregunta 46
Pregunta
What are the common splice connectors for copper (select all correct)
Respuesta
-
straight through
-
butt splice
-
half tap
Pregunta 47
Pregunta
What are the common splice enclosures (select all correct)
Pregunta 48
Pregunta
Which copper splicing method allows the conductors to be folded into the splice and allows for maintenance, rearrangement and transfer of the conductors
Respuesta
-
Inline
-
Foldback
-
Butt
-
Branch
Pregunta 49
Pregunta
What is the minimum bend radius of a 4 pair balanced twisted pair cord
Respuesta
-
1x patch cord diameter
-
4x patch cord diameter
-
4 inches
-
2 inches
Pregunta 50
Pregunta
What is the minimum bend radius of a multipair cable
Pregunta 51
Pregunta
Cable pair twists for CAT3 must be maintained to within ____________ of termination
Respuesta
-
3 inches
-
2 inches
-
1 inch
-
.5 inches
Pregunta 52
Pregunta
Cable pair twists for CAT5e or higher must be maintained to within ____________ of termination
Respuesta
-
.5 inches
-
.25 inches
-
.75 inches
-
1 inch
Pregunta 53
Pregunta
110 blocks come in increments of ________ pairs (select all correct)
Pregunta 54
Pregunta
BIX blocks come in increments of ________ pairs (select all correct)
Pregunta 55
Pregunta
Field terminated patch cables are not recommended for CAT5e
Pregunta 56
Pregunta
What is the most common video connector in the industry
Pregunta 57
Pregunta
Specification and visual inspection is what phase of testing
Pregunta 58
Pregunta
Testing with various test equipment is what phase of testing
Pregunta 59
Pregunta
Documentation is what phase of testing
Pregunta 60
Pregunta
Except in particular cases, what is the maximum length of equipment cords
Pregunta 61
Pregunta
A consolidation point will extend the horizontal cabling length
Pregunta 62
Pregunta
What is the maximum amount of work areas that a MUTOA should serve
Pregunta 63
Pregunta
A minimum of 1 dedicated, non-switched duplex receptacle should be available for equipment in each _________
Pregunta 64
Pregunta
What is the maximum square footage a TE should serve
Pregunta 65
Pregunta
What is minimum recommended cable tray width for an ER, TR or EF
Respuesta
-
12 inches
-
18 inches
-
6 inches
-
24 inches
Pregunta 66
Pregunta
Which grade of plywood has knotholes without any repair
Respuesta
-
Grade A
-
Grade B
-
Grade C
-
Grade D
Pregunta 67
Pregunta
Which grade of plywood contains some blemishes and the occasional knothole
Respuesta
-
Grade A
-
Grade B
-
Grade C
-
Grade D
Pregunta 68
Pregunta
Which grade of plywood has the knotholes cut out and replaced with a patch of clean wood
Respuesta
-
Grade A
-
Grade B
-
Grade C
-
Grade D
Pregunta 69
Pregunta
Which grade of plywood is the highest grade and is without any surface blemishes
Respuesta
-
Grade A
-
Grade B
-
Grade C
-
Grade D
Pregunta 70
Pregunta
Which grade of plywood should be used for ER, TR & EFs
Pregunta 71
Pregunta
How many walls should have plywood installed
Pregunta 72
Pregunta
Select all that apply to backboards in ERs, TRs & EFs
Respuesta
-
3/4" thick plywood
-
at least 2 coats of fire retardant paint
-
minimum 1/4" toggle bolts
-
toggle bolts should be spaced 24 inches
-
toggle bolts should be 2 inches from the edge of the plywood
-
plywood should be mounted 6 inches AFF
Pregunta 73
Pregunta
Most ITS installations will require a 19 inch by 7 ft rack
Pregunta 74
Pregunta
What are the common depths of racks (select all correct)
Pregunta 75
Pregunta
What are the popular thread sizes for racks/cabinets (select all correct)
Pregunta 76
Pregunta
What is the preferred size of patch panels
Pregunta 77
Pregunta
What are the reasons that FMT is not recommended (select all correct)
Respuesta
-
creep
-
shift
-
damage cable sheath
Pregunta 78
Pregunta
If using FMT, what rules must be followed (select all correct)
Pregunta 79
Pregunta
How many 90 degree bends are allowed in conduit segment
Pregunta 80
Pregunta
If more than two 90 degree bends are needed, what must be done (select all correct)
Respuesta
-
run is not longer than 33ft
-
increase conduit 1 trade size
-
install one 90 degree bend within 12 inches of feed end
Pregunta 81
Pregunta
When conduits enter a TR through the floor, how far should they protrude
Respuesta
-
6 inches
-
2-4 inches
-
1-3 inches
Pregunta 82
Pregunta
What are the 3 common depths of basket tray (rod stock tray) (select all correct)
Pregunta 83
Pregunta
This is the portion of the data center that actually houses the IT equipment
Respuesta
-
Computer Room
-
Equipment Room
-
Entrance Room
Pregunta 84
Pregunta
Which types of cables are recognized in data center telecommunications (select all correct)
Pregunta 85
Pregunta
Which two types of coaxial cable does ANSI/TIA 942 recognize for E1, E3 & T3 circuits (select all correct)
Respuesta
-
734-type
-
735-type
-
Series 6
-
Series 11
Pregunta 86
Pregunta
Which type of connectors are installed on 734-type and 735-type coaxial cable for E1, E3 & T3 circuits (select all correct)
Pregunta 87
Pregunta
Cable trays in data centers should be planned for initial maximum calculated fill ratio of ________%
Pregunta 88
Pregunta
How much clearance should be provided above the of cable trays when they are installed above cabinets
Respuesta
-
12 inches
-
10 inches
-
6 inches
-
18 inches
Pregunta 89
Pregunta
How much clearance should be above a cable tray that is installed below a raised floor
Respuesta
-
2 inches
-
3 inches
-
6 inches
-
12 inches
Pregunta 90
Pregunta
Cable trays installed under raised floors in data centers should be installed in the cold aisle
Pregunta 91
Pregunta
In a data center, how much horizontal cable management should be provided for each 1u of patch panel
Pregunta 92
Pregunta
Power strips supporting only single-corded equipment should be loaded no more than _______% of circuit capacity
Pregunta 93
Pregunta
Power strips supporting only dual-corded equipment should be loaded no more than _______% of circuit capacity
Pregunta 94
Pregunta
Some unique aspects of health care regarding access control are (select all correct)
Respuesta
-
elevator controls (cab calls and override)
-
integration will infant protection, wandering patient and elopement systems
-
card readers not always being located at the door
-
multiple levels of access control for care providers, visitors and security
Pregunta 95
Pregunta
In a health care facility, PT (pneumatic tube) system is typically what size tubing
Pregunta 96
Pregunta
Central equipment cabinets are the heart of the system and likely will occupy 4ft x 8ft of wall space in the TR
Pregunta 97
Pregunta
HEPA/ultra-low penetration air (ULPA) vacuum cleaners shall trap _________% of particles 0.12 micrometers and larger
Pregunta 98
Pregunta
In health care facility projects, the safety officer or facilities director shall make at least _________ documented visit(s) per week to each construction work zone
Pregunta 99
Pregunta
This document is the understanding between the customer and the contractor
Respuesta
-
project contract
-
scope of work
-
specifications
Pregunta 100
Pregunta
CLA Series System Drawings: Campus or Site Plans
Pregunta 101
Pregunta
CLA Series System Drawings: Layout of complete building per floor
Pregunta 102
Pregunta
CLA Series System Drawings: Serving Zones: drop locations and cable IDs
Pregunta 103
Pregunta
CLA Series System Drawings: Communication equipment rooms
Pregunta 104
Pregunta
CLA Series System Drawings: Typical detail drawings: face-plate labeling, firestopping
Pregunta 105
Pregunta
CLA Series System Drawings: Schedules
Pregunta 106
Pregunta
What are the 3 major areas in security that may be part of an ITS installer's work (select 3)
Pregunta 107
Pregunta
A fire alarm system should be designed by a licensed fire protection engineer to ensure proper coverage and code compliance
Pregunta 108
Pregunta
DAS consists of an infrastructure of electronic devices including (select all correct)
Respuesta
-
amplifiers
-
cabling
-
connectors
-
antennas
-
hardware
Pregunta 109
Pregunta
This is a device that transmits and receives electromagnetic waves
Respuesta
-
antenna
-
transmitter
-
transceiver
Pregunta 110
Pregunta
Each 6dB increase in an antenna equals the ___________ of the possible range
Pregunta 111
Pregunta
Each 6dB decrease in an antenna equals the ___________ of the possible antenna range
Pregunta 112
Pregunta
The standoffs for a radiating cable need to be _______ inches below the cable tray
Respuesta
-
2 inches
-
3 inches
-
4 inches
-
6 inches
Pregunta 113
Pregunta
Wireless access points should be mounted at least ________ meter(s) from any metal obstructions
Pregunta 114
Pregunta
Most antennas used with APs indoors come with a ______ cable, commonly known as a pigtail
Pregunta 115
Pregunta
What are the 3 common voltages used in centrally amplified systems (select 3)
Pregunta 116
Pregunta
Which paging system operates at 24vdc
Pregunta 117
Pregunta
Which paging system will typically have 2 conductor cable installed
Respuesta
-
centrally amplified
-
distributed amplified
Pregunta 118
Pregunta
What are the 2 common types of sound masking systems (select 2)
Respuesta
-
in-plenum
-
direct-field
-
above ceiling
Pregunta 119
Pregunta
What time each day does the master clock send a longer pulse that corrects all of the secondary clocks to the correct hour
Pregunta 120
Pregunta
D-loading coils are commonly placed by telephone companies at which distance
Pregunta 121
Pregunta
H-loading coils are most commonly placed by the telephone company at which distance
Pregunta 122
Pregunta
Loss for premise cabling, including taps, should not exceed _____ dB of loss