Questão 1

Questão
What does Cg relate to in cable calculations?
Responda
  • Grouping factor
  • Ambient temperature
  • Insulation factor
  • Burred depth factors

Questão 2

Questão
Zs=
Responda
  • R1+R2
  • Ze+R1
  • External loop impedance
  • Earth fault loop impedance

Questão 3

Questão
When calculating maximum Zs for a circuit design what is the 1.2 multiplier used to account for?
Responda
  • Increase in conductor temperature
  • Human error in measurement
  • Decrease in earth fault current
  • Parallel paths

Questão 4

Questão
What is the maximum permissible voltage drop for lighting in a final circuit?
Responda
  • 2.5%
  • 5%
  • 3%
  • It depends on the starting voltage

Questão 5

Questão
What is the formula for voltage drop?
Responda
  • (Ib x Length x mV/A/m)/1000
  • Ib x Length x mV/A/m
  • (In x Length x mV/A/m)/1000
  • In x Length x mV/A/m

Questão 6

Questão
What does In stand for?
Responda
  • Nominal current rating of the protective device
  • Design curent
  • Ingress notation
  • Notional current

Questão 7

Questão
If an RCD is to be for additional protection, how many tests should be carried out on it?
Responda
  • 6
  • 4
  • 3
  • 5

Questão 8

Questão
What is the rated current for an RCD that is to be used as additional protection?
Responda
  • 30mA
  • 50mA
  • 300mA
  • 30A

Questão 9

Questão
What does maintenance factor in lighting design relate to?
Responda
  • The cleanliness of the room
  • The cleanliness of the lamps
  • The lamp deterioration
  • All of the above

Questão 10

Questão
Which out of the following relate to utilisation factor?
Responda
  • Reflectance values of the ceiling, wall and floor
  • How often people are using a room
  • How often the lights are left on when people have left
  • The floor area of the room being lit

Questão 11

Questão
A room is to be illuminated to 350 lux. The maintenance factor is 0.85, utilisation factor is 0.8 and the room measures 6m by 8m. Calculate the number of fittings required if each fitting is 100W and has an efficacy of 70 lumens/watt.
Responda
  • 10
  • 6
  • 4
  • 3

Questão 12

Questão
What maintenance should be carried out on a motor to ensure correct working:
Responda
  • Continuity of windings
  • Insulation resistance of the windings
  • Insulation resistance between the windings and the case
  • Changing of bearings
  • Cleaning of luminaires in room
  • Varnishing of shaft
  • Monthly rotation of end plates

Questão 13

Questão
What types of earthing rely on the distributor's earthing arrangement?
Responda
  • TT
  • TNCS
  • TNS

Questão 14

Questão
How may PFC be obtained?
Responda
  • Calculation, enquiry and measurement
  • Enquiry and measurement
  • Measurement only
  • Enquiry only

Questão 15

Questão
What earthing system has a combined earth and neutral conductor back to the transformer?
Responda
  • TNCS
  • TT
  • IT
  • TNS

Questão 16

Questão
What is the maximum permitted voltage drop for a final power circuit?
Responda
  • 3%
  • 5%
  • 2%
  • 9%

Questão 17

Questão
A fault of negligible impedance between a live conductor and earth is known as?
Responda
  • PSCC
  • PEFC
  • PC
  • PEEC

Questão 18

Questão
How can earth fault loop impedance relate to the disconnection time of a circuit breaker?
Responda
  • Zs relates to fault current
  • Zs relates to RCD operating time
  • Zs relates to nominal voltage
  • Zs relates to full load current of the circuit

Questão 19

Questão
It is acceptable to run single core cables on metal tray
Responda
  • True
  • False

Questão 20

Questão
It is acceptable to run single core cables in metal trunking
Responda
  • True
  • False

Questão 21

Questão
What is the most suitable containment method for an outside motor to be connected to the electrical supply?
Responda
  • SWA
  • Metal conduit
  • Metal trunking
  • Cable basket

Questão 22

Questão
What does Ci relate to in cable calculations?
Responda
  • Thermal insulation
  • Above ordinary current
  • Initial load current
  • Installation

Questão 23

Questão
An installation with a nominal voltage of 230V has an external loop impedance of 0.2Ω and an external line to neutral voltage of 0.18Ω. What would the PFC be recorded on the test certificate?
Responda
  • 1150A
  • 1278A
  • 2kA
  • 1.8kA

Questão 24

Questão
When measuring PSSC the earth should be removed from the installation.
Responda
  • True
  • False

Questão 25

Questão
When measuring PEFC your terminals will be connected between line, neutral and the earth bar.
Responda
  • True
  • False

Questão 26

Questão
Single phase circuit is run in trunking with 3 other circuits. The ambient temperature for the room is 35° . The design current is 33A and the protective device an MCB to BS 60898. What is the minimum size 70° single-core thermoplastic cable that can be used taking into account current carrying capacity only?
Responda
  • 6mm²
  • 10mm²
  • 16mm²
  • 25mm²

Questão 27

Questão
There are 7 x 10mm², 5 x 6mm², 4 x 25mm² and 8 x 2.5mm² single phase circuits to be installed in trunking. Calculate the size required if all cables are PVC BS 6004 cables.
Responda
  • 50mm x 50mm
  • 75mm x 50mm
  • 75mm x 75mm
  • 100 x 75mm

Questão 28

Questão
A 5m run of conduit with 2 bends in it is to accommodate 2 ring final circuits of 2.5mm². Calculate the minimum size conduit to be used.
Responda
  • 32mm
  • 25mm
  • 20mm
  • 16mm

Questão 29

Questão
Electrocution doesn't always result in death
Responda
  • True
  • False

Questão 30

Questão
Which of the following should be included in a risk assessment
Responda
  • Details of the hazard/risk
  • Control measures to be applied
  • Applicable standards to the risk assessment
  • The evaluation of the risks
  • Dates of review
  • Company financial information
  • Serial numbers of PPE equipment
  • Time sheets
  • The address of all contributors to the risk assessment

Questão 31

Questão
A store room must be illuminated to 200 lux. The size of the room is 9m x 10m, the room is kept fairly clean (M.F of 0.9) and due to god colour management and space ratios the U.F is 0.9. Calculate how many light fittings are to be used if each fitting contains 2 lamps of 2000 lumens each.
Responda
  • 3
  • 4
  • 5
  • 6
  • 7

Semelhante

Conjuntos Numéricos
Laura Louis
Phrasal Verbs - Inglês #3
Eduardo .
Fórmulas de Física para Vestibular
GoConqr suporte .
DIREITO PROCESSUAL PENAL
Joelma Silva
Flashcards de Inglês - Vocabulário Intermédio
ARLEY MARINHO
O BARROCO
Luís Pita
FCE Practice Quiz - B2
titaleoni
Gestão por Competências
alexrocksilva
Questões Grécia Antiga- Antiguidade Classica
vesanso Souza
Planejamento e Controle da Produção
Luciana Amaral Pereira Freire
Grécia Clássica
jacson luft