5 Cable Installation

Beschreibung

Class quiz (Class Quiz) Quiz am 5 Cable Installation, erstellt von Jeanie Fitzgerald am 20/07/2017.
Jeanie Fitzgerald
Quiz von Jeanie Fitzgerald, aktualisiert more than 1 year ago
Jeanie Fitzgerald
Erstellt von Jeanie Fitzgerald vor mehr als 7 Jahre
83
2

Zusammenfassung der Ressource

Frage 1

Frage
Minimum bend radius for balanced twisted pair 4- pair during installation
Antworten
  • twice the diameter of cable
  • four times diameter of cable
  • 2 inches
  • 4 inches

Frage 2

Frage
Minimum bend radius for Intrabuilding optical fiber during installation
Antworten
  • 10 times outside diameter
  • 15 times outside diameter
  • 20 times outside diameter

Frage 3

Frage
Minimum bend radius for Backbone Optical fiber at rest
Antworten
  • 10 times outside diameter
  • 15 times outside diameter
  • 20 times outside diameter

Frage 4

Frage
Minimum bend radius Interbuilding optical fiber during installation
Antworten
  • 10 times outside diameter
  • 15 times outside diameter
  • 20 times outside diameter

Frage 5

Frage
Before work begins, it is important to secure the area to ________________ access to unauthorized personnel only.
Antworten
  • Allow
  • Permit
  • Restrict

Frage 6

Frage
What can be used to designate a work zone, area (select all that apply)
Antworten
  • safety cones
  • yellow tape
  • folding A frame signs

Frage 7

Frage
What is the most common environmental hazards faced by the installer
Antworten
  • Falls and trip hazards
  • chemical hazards
  • electrical wires or equipment

Frage 8

Frage
All firestopping solutions area a combination of fire stop materials, devices, packing materials that make up a listed system. Use only __________ __________ to properly restore the penetration of any fire or smoke rated barrier.
Antworten
  • Approved methods
  • Approved materials
  • Listed assembies

Frage 9

Frage
As-built drawings are sometimes called record drawings to the general contractor or building owner.
Antworten
  • True
  • False

Frage 10

Frage
What tasks should be done after the cable is pulled ( select all that apply )
Antworten
  • Label all ICT components
  • Update the building floor plans
  • Perform housekeeping items

Frage 11

Frage
Allow no more than two 90 degree bends per 30 m = (100 ft) pull if in conduit
Antworten
  • True
  • False

Frage 12

Frage
Controlling bend radius and friction can prevent damage to the cable. A ___ in. diameter smooth static pipe or ____ in. roller will help to maintain proper bend radius limits.
Antworten
  • 2, 1
  • 3, 2
  • 4, 3

Frage 13

Frage
Service slack for ____________ ____________ shall reach the farthest corner of the TR via pathways and add the distance from floor to ceiling.
Antworten
  • Copper backbone cables
  • Horizontal copper cables
  • Optical fiber cables

Frage 14

Frage
_____________ _____________ shall have enough slack to reach the farthest corner of the backboard via pathway in case new equipment is added later.
Antworten
  • Copper backbone
  • Horizontal cables
  • Optical fiber

Frage 15

Frage
Optical fiber backbone cables shall require the same slack as optical fiber horizontal cables.
Antworten
  • True
  • False

Frage 16

Frage
Balanced twisted pair horizontal cables shall have _______ of slack left in the work area to allow for ______ after termination. Cables shall not be stored in loops.
Antworten
  • 1 ft. - 1.6 ft.
  • 1.6 ft. - 1 ft.
  • 10 ft. - 3.3 ft.

Frage 17

Frage
Optical fiber cables shall have 1 m = (3.3 ft. ) of slack left in the work area to allow for termination.
Antworten
  • True
  • False

Frage 18

Frage
A conduit 2 in. or less must maintain a bend radius of at least ____ times the internal conduit diameter.
Antworten
  • 6
  • 8
  • 10

Frage 19

Frage
A conduit greater than 2 in. should maintain a bend radius of at least ___ times the internal conduit diameter.
Antworten
  • 6
  • 8
  • 10

Frage 20

Frage
The maximum pull force for 4 pair 24 AWG cable is ___ lbf. the maximum pull force for two to four strand optical fiber is ___ lbf.
Antworten
  • 20, 40
  • 25, 50
  • 25, 75

Frage 21

Frage
It is acceptable to use structural steel ( red iron ) to directly support cables.
Antworten
  • True
  • False

Frage 22

Frage
Pull string tensile strength ratings range from ______ to ______ lbf.
Antworten
  • 50 - 200
  • 75- 200
  • 75- 225

Frage 23

Frage
Only tested and accepted lengths of optical fiber are to be installed. What test instruments are typically used to test optical fiber on the reel? select all that apply
Antworten
  • Visual fault locator (VFL)
  • Optical loss test set (OLTS)
  • Optical time domain reflectometer (OTDR)

Frage 24

Frage
Which test instrument requires access to both ends of the cable?
Antworten
  • VFL
  • OTDR
  • OLTS

Frage 25

Frage
Where optical fiber cables will be used, consider placing three innerducts ( two 1.5 in. and one 1 in. ) inside each _______ conduit.
Antworten
  • 4 in.
  • 6 in.
  • 8 in.

Frage 26

Frage
Placing the optical fiber cables in a multi-weave wire mesh grip of appropriate size that has a swivel pulling eye is the preferred method for attaching this fiber to a pull rope
Antworten
  • loose tube
  • tight buffer
  • ribbon

Frage 27

Frage
Preferred method for attaching tight buffer fiber to a pull rope
Antworten
  • securing aramid yarn strength member
  • wire mesh grip
  • 3 half hitches and a knot

Frage 28

Frage
How much optical fiber cable slack should be left at the at the work area
Antworten
  • 3.3 ft.
  • 10 ft.
  • farthest point of work area

Frage 29

Frage
In air blown fiber, fluid drag is what carries the cable down the tube
Antworten
  • True
  • False

Frage 30

Frage
Air blown fiber is only recommended for inside plant applications.
Antworten
  • True
  • False

Frage 31

Frage
In air blown optical fiber installations, air pressure is typically between ______and ______ psi.
Antworten
  • 75- 200
  • 150- 220
  • 150- 250

Frage 32

Frage
This cable shall have enough slack to reach the farthest corner of the TR via pathways, add floor to ceiling and an additional 10 feet. (Select all that apply )
Antworten
  • Horizontal Optical fiber
  • Backbone Optical fiber
  • Copper backbone
  • Horizontal Copper
Zusammenfassung anzeigen Zusammenfassung ausblenden

ähnlicher Inhalt

Einstufungstest Englisch
SprachschuleAktiv
PuKW - STEP 1 (mögliche Prüfungsfragen/Prüfungsvorbereitung)
frau planlos
IKA-Theoriefragen Serie 17 (15 Fragen)
IKA ON ICT GmbH
BM 13 - Allgemeine Didaktik
Isabell St
Financial Accounting
zok42.com
PuKW - GESKO PR
Elisa Kosch
AOW-Psychologie SS18
Anna Huber
Forschungs- und Anwendungsfelder der Soziologie Teil 3
stelly Welly
EC- Entwicklungspsychologie 1
Michael B
Juristische Wirtschaftskompetenz
Lisa Stüttler
Vetie: Milch 2020 Matrikel 14
Johanna Tr